Ventilation in ASHRAE 62.1 is not a single number per square foot. It has two components, and skipping either one leads to IAQ complaints or energy waste.

The formula

Vbz = Rp × Pz + Ra × Az Where: Vbz = breathing zone outdoor airflow (CFM) Rp = per-person outdoor air rate (CFM/person) Pz = zone population (number of people) Ra = per-area outdoor air rate (CFM/ft²) Az = zone floor area (ft²) 

The people component (Rp × Pz) handles CO2, bioeffluents, and body odor. The area component (Ra × Az) handles off-gassing from materials, furniture, and finishes.

Rates by space type

Space Type Rp (CFM/person) Ra (CFM/ft²) ────────────────────────────────────────────────────── Office 5 0.06 Conference room 5 0.06 Classroom (age 9+) 10 0.12 Lecture hall 7.5 0.06 Retail sales floor 7.5 0.12 Restaurant dining 7.5 0.18 Gym / exercise room 20 0.06 Hotel bedroom 5 0.06 Lobby / waiting 7.5 0.06 Beauty salon 20 0.12 

Notice: gym and salon require 20 CFM/person — 4× the office rate.

Example: conference room

Room: 500 ft², seats 20 people Rp = 5 CFM/person, Ra = 0.06 CFM/ft² Correct ventilation: Vbz = 5 × 20 + 0.06 × 500 = 100 + 30 = 130 CFM outdoor air Sized for "normal" occupancy (5 people): Vbz = 5 × 5 + 0.06 × 500 = 25 + 30 = 55 CFM outdoor air 

55 CFM vs 130 CFM needed. The room gets less than half the required ventilation when full. CO2 climbs to 1,800 ppm by mid-afternoon.

Example: open office vs classroom

Same 1,000 ft² room, 25 occupants: Open office: Vbz = 5 × 25 + 0.06 × 1,000 = 125 + 60 = 185 CFM Classroom: Vbz = 10 × 25 + 0.12 × 1,000 = 250 + 120 = 370 CFM 

Same room, same people count. The classroom needs double the ventilation because both Rp and Ra are higher.

The energy cost of getting it wrong

Excess outdoor air at 95F cooled to 75F: Per 100 CFM excess: Q = 1.08 × 100 × 20 = 2,160 BTU/hr Cost at $0.12/kWh ≈ $0.08/hour Cooling season (2,000 hrs) ≈ $160 Per 100 CFM deficit: CO2 rises → complaints → productivity loss Estimated cost: $50-100/person/year in lost focus 

The check

1. Identify space type → look up Rp and Ra 2. Determine design occupancy (not average — peak) 3. Calculate: Vbz = Rp × people + Ra × area 4. Verify the outdoor air damper delivers this CFM 5. For variable occupancy: consider DCV (CO2 sensor) 

Ventilation is not just about comfort. It is a code requirement. ASHRAE 62.1 is referenced by IBC, UMC, and most local codes.