Choose between Armstrong LS and MS traps by load
A float and thermostatic trap has to do two jobs at once. The float dumps condensate as it forms, and the thermostatic vent purges air so the coil can heat evenly. The Armstrong LS and MS series are heavy duty ultra capacity traps built for that work. The two families share a body and envelope, but they are not interchangeable. The deciding factor is the load you must pass.
LS or MS
The LS series comes in three pipe sizes: 2 inch (50 mm) as LS8, 2-1/2 inch (65 mm) as LS10, and 3 inch (80 mm) as LS12. All three share a peak capacity of 51,000 lb per hour. The MS series is offered only in the 3 inch (80 mm) size as MS12, and it reaches 280,000 lb per hour, or 127,000 kg per hour. If your condensate load sits near the top of an LS, step to the MS rather than pushing the smaller trap.
The pressure rated designations run 30-LS, 100-LS, 150-LS, 250-LS, 250-MS, 450-LS, and 450-MS. The number is the maximum saturated steam operating pressure in psig. So a 250-LS is rated for 250 psig (17 bar), and a 450-MS for 450 psig (31 bar).
Build and connections
Body and cap are ASTM A216 WCB cast steel. All internal parts, including floats, lever mechanisms, valves, and seats, are 304 stainless steel. The drain plug is carbon steel. The air vent is a stainless and bronze assembly with a balanced pressure phosphor bronze bellows in a stainless cage.
Connections come as screwed NPT or BSPT, socketweld, or flanged PN40. Across all three sizes, height and length are 508 mm, width is 387 mm, bottom to centreline is 106 mm, and centreline to centreline is 287 mm. Screwed and socketweld units weigh 131.5 kg. Flanged PN40 units weigh 137.5 kg at 2 inch, 140.5 kg at 2-1/2 inch, and 143.5 kg at 3 inch. Check these figures against the pipe support design before you lift the trap into place.
The vent limit that catches people out
The thermostatic air vent works from zero up to 250 psig (17 bar), with a peak bellows temperature of 422°F (217°C). Above 250 psig, the vent must be omitted, and only the CC or LD versions are allowed. The vessel design limit for both series is 450 psig at 650°F (31 bar at 343°C), but that does not mean the standard vent survives at that pressure. Pick the version to match the pressure, not just the body rating.
Suffixes worth knowing
The VB suffix adds an integral vacuum breaker, capped at 150 psig (10 bar). The LD suffix is a liquid drainer with no internal air vent, for draining water from pressurised gas or air, with a top port for a back vent. The CC suffix is a condensate controller for syphon drainage, where condensate lifts to the trap, using a fixed restricted upper orifice to vent air and flash steam. The GG suffix is an armoured gauge glass rated 250 psig at 424°F (17 bar at 218°C). A floor mounting bracket is available for both series.
Warm up slowly
Heat the unit sequentially at no more than 100°F (55°C) every 8 minutes. Rushing the warm up risks thermal stress and water hammer that can damage the valve, fittings, piping, and heat exchange gear. Above 30 psig (2 bar) or in harsh service, fit an anchoring bracket or equivalent support to limit pipe stress. When the load approaches the trap capacity, enlarge the discharge pipe by one size as close to the cap as practical.
On a vacuum service, remember that vacuum holds condensate upstream. A vacuum breaker admits air to clear it. On modulated heating coils, pair the breaker with freeze protection to guard against both freezing and water hammer.
See the dimensional reference page for the full size table, the connection options, and the capacity data for each designation.