arXiv:2611.17661v1 Announce Type: new Abstract: Damping control of a forced oscillation may reduce amplitudes at certain locations while increasing them elsewhere. This paper introduces Pareto improvement as a criterion for assessing such control: at least one nodal oscillation amplitude decreases, while none increases across all other nodes. The analysis considers active-power forcing sources and active-power control injections in connected swing networks with positive inertia and damping. Necessary conditions for Pareto improvement feasibility are derived from the normalized nodal responses. It is proven that for every network with a single oscillation source and a single actuator, at least one positive forcing frequency is shown to preclude Pareto improvement, regardless of the amplitude and phase of the control input. A three-node counterexample shows that this limitation does not persist with multiple actuators. PSS/E simulations of a 6-bus benchmark system and a modified IEEE 39-bus system validated the analysis. These findings suggest the value of assessing control effects across the network and further investigating multi-actuator damping control.